Compact (UK) Ltd

Unit 8 Mayfield Avenue Industrial Park,
Fyfield Road, Weyhill, Nr Andover,
Hampshire SP11 8HU

Tel: 01264 772173 or 0800 612 1099 Fax: 01264 773961
E-mail: sales@compactaircon.co.uk

MINI CD/U CHILLED WATER RANGE (CD/UCW05-19)
TOTAL COOLING CAPACITY
CD/UCW05
CD/UCW08
CD/UCW10
CD/UCW13
CD/UCW17
CD/UCW19
Chilled Water
ON 7ºC
OFF 12ºC
In Room
24ºC 45%Rh
kW
5.8
8.9
9.9
13.1
16.7
18.8
Cooling Stages
3 Port Modulating Valve
FAN DATA
Air Volume³
M³/s
0.44
0.64
0.74
0.94
1.15
1.3
Number of Fans
1
1
1
2
2
2
Fan Motor Rated Power
W
1x750
1x750
1x750
2x750
2x750
2x750
HEATING DATA
Heater Capacity
kW
3
3
3
9
9
9
Electric Heater Stages
1
1
1
1
1
1
HUMIDIFIER DATA
Humidification Capacity
Kg/h
2.5
2.5
2.5
2.5

2.5

2.5
Humidifier Power Input (Max)
kW
2.0
2.0
2.0
2.0
2.0
2.0
Humidifier Stages
1
1
1
1
1
1
ELECTRICAL DATA
Power Requirements 4380/415V 3ph 50Hz
25A
25A
25A
25A
25A
25A
WEIGHTS
AHU Weight CD/U05-19
Kg
166
170
174
221
270
286
Unit Dimensions
mm
W 790 x H 1800 x D 530
W 1290 x H 1800 x D 530


NOTES: MINI CD/U CHILLED WATER RANGE:
1. The above duties are based on Chilled Water ON to the Unit at 7ºC and OFF the Unit at 12ºC.
2. In Room Condition is based on 24ºC 45% RH
3. The stated duties refer to the evaporator coil and DO NOT include fan gains.
4. The quoted airflows are subject to a tolerance of ±5%
5. The recommended power supply is based on maximum current demand during automatic operation.
© Compact (UK) Ltd All Rights Reserved

click here to close window