MINI CD/U
CHILLED WATER RANGE (CD/UCW05-19)
| TOTAL COOLING CAPACITY |
CD/UCW05
|
CD/UCW08
|
CD/UCW10
|
CD/UCW13
|
CD/UCW17
|
CD/UCW19
|
Chilled Water
ON 7ºC
OFF 12ºC |
In Room
24ºC 45%Rh |
kW
|
5.8
|
8.9
|
9.9
|
13.1
|
16.7
|
18.8
|
| Cooling Stages |
3 Port Modulating Valve
|
| FAN DATA
|
| Air Volume³ |
M³/s
|
0.44
|
0.64
|
0.74
|
0.94
|
1.15
|
1.3
|
| Number of Fans |
1
|
1
|
1
|
2
|
2
|
2
|
| Fan Motor Rated Power |
W
|
1x750
|
1x750
|
1x750
|
2x750
|
2x750
|
2x750
|
|
HEATING DATA
|
| Heater Capacity |
kW
|
3
|
3
|
3
|
9
|
9
|
9
|
| Electric Heater Stages |
1
|
1
|
1
|
1
|
1
|
1
|
| HUMIDIFIER
DATA |
| Humidification Capacity |
Kg/h
|
2.5
|
2.5
|
2.5
|
2.5
|
2.5
|
2.5
|
| Humidifier Power Input (Max) |
kW
|
2.0
|
2.0
|
2.0
|
2.0
|
2.0
|
2.0
|
| Humidifier Stages |
1
|
1
|
1
|
1
|
1
|
1
|
| ELECTRICAL
DATA |
| Power Requirements 4380/415V
3ph 50Hz |
25A
|
25A
|
25A
|
25A
|
25A
|
25A
|
| WEIGHTS |
| AHU Weight CD/U05-19 |
Kg
|
166
|
170
|
174
|
221
|
270
|
286
|
| Unit Dimensions |
mm
|
W 790 x H 1800 x D 530
|
W 1290 x H 1800 x D 530
|
NOTES: MINI CD/U CHILLED WATER RANGE:
1. The above duties are based on Chilled Water ON to the Unit
at 7ºC and OFF the Unit at 12ºC.
2. In Room Condition is based on 24ºC 45% RH
3. The stated duties refer to the evaporator coil and DO NOT include
fan gains.
4. The quoted airflows are subject to a tolerance of ±5%
5. The recommended power supply is based on maximum current demand
during automatic operation.
|