CD/U CHILLED
WATER RANGE (CD/U30-111)
| TOTAL COOLING CAPACITY |
CD/U30
|
CD/U45
|
CD/U60
|
CD/U75
|
CD/U100
|
CD/U111
|
Chilled Water
ON 7ºC
OFF 12ºC |
In Room
24ºC 45%Rh |
kW
|
29
|
46
|
61
|
76
|
96
|
109
|
| Cooling Stages |
3 Port Modulating Valve
|
| FAN DATA
|
| Air Volume³ |
M³/s
|
3.0
|
3.6
|
4.9
|
5.4
|
5.9
|
6.8
|
| Number of Fans |
2
|
2
|
2
|
2
|
2
|
2
|
| Fan Motor Rated Power |
kW
|
2x2.2
|
2x2.2
|
2x3.0
|
2x3.0
|
2x3.0
|
2x4.0
|
|
HEATING DATA
|
| Heater Capacity |
kW
|
10.5
|
10.5
|
15
|
15
|
15
|
15
|
| Electric Heater Stages |
3
|
3
|
3
|
3
|
3
|
3
|
| LPHW Heater Stages
(optional) |
2
|
2
|
2
|
2
|
2
|
2
|
| HUMIDIFIER
DATA |
| Humidification Capacity |
Kg/h
|
3.0
|
5.5
|
5.5
|
7.0
|
10
|
10
|
| Humidifier Power Input (Max) |
kW
|
2.4
|
4.4
|
4.4
|
5.6
|
8.0
|
8.0
|
| Humidifier Stages |
1
|
1
|
1
|
1
|
1
|
1
|
| ELECTRICAL
DATA |
| Power Requirements 4380/415V
3ph 50Hz |
40A
|
40A
|
60A
|
60A
|
60A
|
100A
|
| WEIGHTS |
| AHU Weight CD/U35-111 |
Kg
|
310
|
350
|
480
|
500
|
530
|
575
|
| Unit Dimensions |
mm
|
W 1384 x H 1950
x D874
|
W 2054 x H 1950
x D 874
|
NOTES: CD/U CHILLED WATER RANGE:
1. The above duties are based on Chilled Water ON to the Unit
at 7ºC and OFF the Unit at 12ºC.
2. In Room Condition is based on 24ºC 45% RH
3. The stated duties refer to the evaporator coil and DO NOT include
fan gains.
4. The quoted airflows are subject to a tolerance of ±5%
5. The recommended power supply is based on maximum current demand
during automatic operation.
|