Compact (UK) Ltd

Unit 8 Mayfield Avenue Industrial Park,
Fyfield Road, Weyhill, Nr Andover,
Hampshire SP11 8HU

Tel: 01264 772173 or 0800 612 1099 Fax: 01264 773961
E-mail: sales@compactaircon.co.uk

CD/U RANGE WITH REMOTE CONDENSING UNITS (CD/U15-90)
OR WITH REMOTE AIR COOLED CONDENSERS (CD/U15-90)

TOTAL COOLING CAPACITY
CD/U15
CD/U20
CD/U30
CD/U40
CD/U50
CD/U60
CD/U80
CD/U90
Ambient 30ºC In Room 22.2ºC
kW
13.2
18.4
28.1
36.9
42.2
55.4
73.8
82.4
In Room 23.9ºC
kW
14.2
19.8
30.2
39.7
45.3
59.3
79.3
85.3
Sensible Heat Ratio 22.2ºC 50%Rh
0.99
0.99
0.99
0.99
0.99
0.99
0.99
0.97
23.9ºC 45%Rh
0.99
0.99
0.99
0.99
0.99
0.99
0.99
0.97
Cooling Stages
2
3
4
4
3
3
4
5
Condensing Unit Models/Quantity
1xCRCU
1xCRCU
5
2xCRCU
4
2xCRCU
5
3xCRCU
4
3xCRCU
5
4xCRCU
5
5xCRCU
5.5
Condenser Unit Models/Quantity
1xCRAC
21  
1xCRAC
24
2xCRAC
21
2xCRAC
24
3xCRAC
21
3xCRAC
24
4xCRAC
24
5xCRAC
30
FAN DATA
Air Volume³
M³/s
1.01 
1.65
2.48
3.30
3.72
4.95
6.61
6.85
Number of Fans
 2
2
2
2
2
2
2
2
Fan Motor Rated Power
kW
2x1.5
2x1.5
2x1.5
2x2.2
2x3.0
2x3.0
2x4.0
2x4.0
HEATING DATA
Heater Capacity
kW
10.5
15
10.5
15
10.5
15
15
15
Electric Heater Stages
3
3
3
3
3
3
3
3
LPHW Heater Stages (optional)
2
2
2
2
2
2
2
2
HUMIDIFIER DATA
Humidification Capacity
Kg/h
2.5
2.5
5.0
5.0

5.0

7.5
10.0
10.0
Humidifier Power Input (Max)
kW
2.0
2.0
4.0
4.0
4.0
6.0
8.0
8.0
Humidifier Stages
1
1
1
1
1
1
1
1
DEHUMIDIFICATION DATA
Dehumidification Capacity
Kg/h
2.5
4.6
3.5
4.6
3.5
4.6
4.6
4.6
ELECTRICAL DATA
Power Requirements 4380/415V 3ph 50Hz
42A
60A
60A
60A
100A
100A
100A
125A
WEIGHTS
AHU Weight CD/U15-90
Kg
290
358
370
485
525
655
705
790
AHU Weight CD/U15-90
incl. Inbuilt Compressors (optional)
Kg
 355
422
498
619
717
856
975
n/a 
Unit Dimensions
mm
W 1384 x H 1950 x D 874
W 2054 x H 1950 x D 874
 
CONDENSING UNITS (for the CD/U15-90 Product Range)
 
CRCU4
CRCU5
CRCU5.5
Air Volume
M³/s
1.77
1.53
1.53
Nominal Fan Power
kW
1x0.53
1x0.53
1x0.53
Nominal Compressor Power
kW
1x4.2
1x5.4
1x5.7
Weight (dry)
Kg
120
140
141
REMOTE CONDENSERS(for the CD/U15-90 Product Range)
 
CRAC21
CRAC24
CRAC30
Air Volume³
M³/s
1.51
1.64
2.85
Nominal Fan Power
kW
1x0.36
1x0.36
2x0.36
Weight (dry)
Kg
40
46
48

NOTES: CD/U RANGE with Remote Condensing Units and Remote Air Cooled Condensers:
1 . The above duties are based on a maximum pressure drop in the refrigerant line of 3 psig (0.21 Bar) and for every extra 1 psig (0.07 Bar) above this, an anticipated reduction of 2% will occur
2. The stated duties refer to the evaporator coil and DO NOT include the fan gains.
3. The quoted airflows are subject to a tolerance of ±5%
4. The recommended power supply is based on maximum current demand during automatic operation.
© Compact (UK) Ltd All Rights Reserved

click here to close window