TOTAL COOLING CAPACITY
CD/U05
CD/U08
CD/U10
CD/U13
CD/U17
CD/U19
Ambient 30ºC In Room 24ºC 45%RH
kW
5.5
8.2
9.5
12.2
17.9
19
Sensible Heat Ratio
0.9
0.9
0.9
0.9
0.9
0.9
Cooling Stages
1
1
1
1
1
1
Condensing Unit Models/Quantity
1xCRCU
2
1xCRCU
3
1xCRCU
3
1xCRCU
4
1xCRCU
5
1xCRCU
5.5
Condenser Unit Models/Quantity
1xCRAC
11
1xCRAC
16
1xCRAC
16
1xCRAC
21
1xCRAC
24
1xCRAC
30
FAN DATA
Air Volume³
M³/s
0.48
0.56
0.64
0.95
1.16
1.25
Number of Fans
1
1
1
2
2
2
Fan Motor Rated Power
W
1x750
1x750
1x750
2x750
2x750
2x750
HEATING DATA
Heater Capacity
kW
3
3
3
9
9
9
Electric Heater Stages
1
1
1
1
1
1
HUMIDIFIER DATA
Humidification Capacity
Kg/h
2.5
2.5
2.5
2.5

2.5

2.5
Humidifier Power Input (Max)
kW
2.0
2.0
2.0
2.0
2.0
2.0
Humidifier Stages
1
1
1
1
1
1
DEHUMIDIFICATION DATA
Dehumidification Capacity
Kg/h
2.0
2.0
2.0
2.0
2.0
2.0
ELECTRICAL DATA
Power Requirements 4380/415V 3ph 50Hz
20A
25A
25A
35A
45A
60A
WEIGHTS
AHU Weight CD/U5-19
Kg
166
170
174
221
270
286
AHU Weight CD/U5-19
incl. Inbuilt Compressors (optional)
Kg
177
181
185
232
281
297
Unit Dimensions
mm
W 790 x H 1800 x D 530
W 1290 x H 1800 x D 530
CONDENSING UNITS (for the CD/U05-19 Product Range)
 
CRCU4
CRCU5
CRCU5.5
Air Volume
M³/s
1.77
1.53
1.53
Nominal Fan Power
kW
1x0.53
1x0.53
1x0.53
Nominal Compressor Power
kW
1x4.2
1x5.4
1x5.7
Weight (dry)
Kg
120
140
141
REMOTE CONDENSERS(for the CD/U05-19 Product Range)
 
CRAC11
CRAC16
CRAC21
CRAC24
CRAC30
Air Volume³
M³/s
0.75
1.29
1.51
1.64
2.85
Nominal Fan Power
kW
1x0.135
1x0.36
1x0.36
1x0.36
2x0.36
Weight (dry)
Kg
34
36
40
46
48


NOTES: CD/U RANGE with Remote Condensing Units and Remote Air Cooled Condensers:
1 . The above duties are based on a maximum pressure drop in the refrigerant line of 3 psig (0.21 Bar) and for every extra 1 psig (0.07 Bar) above this, an anticipated reduction of 2% will occur
2. The stated duties refer to the evaporator coil and DO NOT include the fan gains.
3. The quoted airflows are subject to a tolerance of ±5%
4. The recommended power supply is based on maximum current demand during automatic operation.
© Compact (UK) Ltd All Rights Reserved